SRL Insertion Series Models / Specifications
Models
Your Pipe Size Insertion Models1 Max Full Scale (SCFM)2, 3
1" SRL-05-12 200
1-1/4" SRL-05-12 300
1-1/2" SRL-05-12 470
2" SRL-05-15 820
2-1/2" SRL-05-15 1000
3" SRL-05-15 1750
4" SRL-05-15 3150
6"-14" SRL-05-18 33,000
16"-24" SRL-05-24 100,000
26"-36" SRL-05-30 250,000
>36" Consult Factory Consult Factory
1 - "05" refers to probe diameter of 1/2". Optionally, 3/4" probes are available ("07"). The length of probe is typically 15 inches ("15") or 18 inches ("18")
2 - Max Full Scale available for many gases, such as pressurized Air or Nitrogen. Some gases such as Hydrogen may be limited. Contact Sage for details
3 - SCFM = Standard Cubic Feet Per Minute. 1 SCFM = 1.7 NCMH. Sage standard conditions for calibration are 70°F and 29.92" Hg. Note, Max Full Scale is based on a maximum Velocity of 35,000 Standard Feet Per Minute (SFPM)
 
Specifications
 
General
Function Microprocessor-based Insertion Mass Flow Meters for gases
Flow Element Constant Temperature Thermal Mass Flow Element consists of two
316 SS clad platinum-wound RTDs
Flow Rate Output Signal 4-20 ma isolated output linearly proportional to mass flow rate
Temperature Output Signal 0-5 VDC linear temperature signal from 40°F to 200°F (-40°F to 750 °F, optional)
(i.e. this product has both a flow and temperature output)
Power 24 VDC with current dissipation of less than 250 ma,
or 115VAC/230 VAC
Communication RS232 Communication Menuing Software (optional)
Sensor Drive Circuit Proprietary Sensor Drive Circuit provides enhanced flow signal stability and insensitivity to process temperature changes
Display / Keypad SRL Model is a blind format (no Display or Keypad). Remote styles do not require
electronics at sensor Junction Box
Menu Navigation RS232 Communication and Menuing Software (available) upon request
 
Flow Range / Sizes
Units of Measurement Flow–SCFM, SCFH, SCFD, SCCM, NCMM, NCMH, KG/S, KG/M, KG/H, KG/D, LBS/S, LBS/M, LBS/H, LBS/D, SLPM, SLPH; Velocity– SFPM, SFPS,NMPM,NMPS,NMPH (other combinations available); Temperature–°C and °F
Insertion Meters Full Scale depends on pipe size. For example up to 1000 SCFM
in a 2 1/2" pipe, but up to 100,000 SCFM in a 24" pipe
 
Performance
Standard Flow Accuracy +/-1% of Reading +0.5% of Full Scale
Repeatability 0.2% of Full Scale
Turndown Up to 1000:1
Calibration Sage Metering’s National Institute of Standards Traceable (NIST) calibration facility
Gas Temperature Std.: -40°F to 200°F (-40°C to 93°C ); HT01: 200°F to 350°F (93°C to 177°C ); HT02: 350°F to 500°F (177°C to 260°C); HT03: 500°F to 750°F (260°C to 399°C)
Remote Enclosure Temperature 0° to 150°F (-18°C to 65°C ). Contact Sage for lower temperature ranges
Pressure Rating 500 psig (1000 psig optional)
Response Time 1 second (each time constant) for flow change
Pulsed Outputs Configurable for Pulsed Outputs of Totalized Flow
(in lieu of Flow Rate and Temperature)
Wetted Parts 316L Stainless Steel for Flow Bodies, Sensor Flow Elements and Flow Conditioners. Hastelloy (recommended for Chlorine Gas) and other materials optional
Limited Warranty Sage Metering's Series of Thermal Mass Flow Meters are warranted against faulty materials or workmanship for one year from the date of delivery to the buyer. After issuance of a Return Meter Authorization (RMA) by Sage, and upon receipt of the defective meter, Sage will either repair or replace the defective meter at its sole option and at no cost to the purchaser

To get started on your application, or contact us, use the button below on any page.

 

To view or print this page as a PDF formatted file use the button below.
Application Button
 
Print Page

 

Home | Brochure | Contact Us | Application Form | Profiles | Instruction Manual | Links


All Rights Reserved. ©2002-2007 SAGE METERING, INC. 8 Harris Court, Building D1, Monterey, CA 93940
Toll Free (U.S. only): 1-866-677-SAGE (7243) • 1-831-242-2030 • Email:sales@sagemetering.com